HOW does the LEV Monitor work?
The LEV Monitor can be supplied as either a Direct or Remote Mount solution. Fixing the monitor directly to the duct provides a compact anti-tamper solution with no accessible hoses or probes. For applications when space is limited, the Remote mount monitor can be located remotely and is provided with a duct fixing kit including a hose and spigot.
Once the LEV Monitor has been secured into place and the batteries are inserted (2x AA), a static Cross will display to indicate that calibration is complete. The LEV system should then be balanced ensuring that the air flow rates meet the minimum requirements for the specific system, and calibration is as straight forward as pressing a button.
Following calibration the LEV Monitor will display an animated Arrow, accompanied by an ultra-bright Green LED to provide assurance that the system is operating correctly and safely. If the air flow rates drop below the set threshold, the LEV Monitor will display a flashing Cross accompanied by a Red LED to advise that action needs taking!
It also comes with a built-in timer to advise that the LEV system is overdue a Thorough Examination and Test (TExT). The timer can be easily adjusted to 3, 6 or 14 Months. We strongly recommend that the batteries be replaced each time the LEV system is inspected.
With a range of 2,000 Pa the LEV Monitor is suitable for use with most systems, and as an added safety feature, a minimum set point of 100 Pa is in place to ensure that the system cannot be calibrated when the LEV system is not running